How Do Mode 1 and Mode 2 Work Together?

The calculator coordinates two independent tabs: Inflow & TDH System Curve (Mode 1) estimates sustained inflow from a timed basin rise and generates your plumbing's TDH system-curve checkpoints (0, 20, 35, 50 GPM) so you can compare them against a pump's published performance curve, and Backup Battery Runtime (Mode 2) converts usable battery watt-hours, battery-side power draw, standby draw, and duty cycle into estimated runtime hours while flagging inflow deficits.

Mode 1: Inflow & TDH System Curve Inputs and Outputs

Calculator Input Unit / Format Engineering Role
Basin Inside Diameter (D_basin) 18 in, 24 in, or custom in Models a straight empty vertical-wall basin (1.10 gal/in at 18 in, 1.96 gal/in at 24 in)
Measured Water Rise (Delta_h) in Vertical water rise measured during pump-off interval
Pump-Off Interval (t_rise) min Elapsed time for Delta_h to compute sustained inflow (GPM)
Static Vertical Lift (H_static) ft Vertical elevation from minimum sump water level to discharge high point
Straight Discharge Pipe Length (L) ft Single-diameter straight pipe length (uses Sch 40 PVC Hazen-Williams C = 150)
Discharge Pipe Inside Diameter (d_in) 1.5-in (1.610 in) or 2-in (2.067 in) Actual Sch 40 PVC ID; sets both pipe friction and fitting equivalent length
90° Elbows whole count Adds 4.0 ft (1.5-in) or 5.2 ft (2-in) equivalent length per elbow inside friction only
Check Valve One valve or None Adds 10.0 ft (1.5-in) or 13.0 ft (2-in) equivalent length inside friction only
Peak Storm Design Margin (designMargin) 1.0× (default), 1.25×, or 1.5× Multiplies measured inflow (GPM) to compute target design flow and target TDH checkpoint (for example, 18-in ID pit rising 6 in in 1 min = 6.61 GPM, and 1.5× margin = 9.92 GPM)

Mode 1 Outputs: Basin capacity (gal/in), sustained inflow (GPM), optional target design flow (GPM when designMargin > 1), total fittings equivalent length (ft), TDH at measured inflow (ft) and at target design flow (ft), and a 4-point System Curve Checkpoints table (0, 20, 35, 50 GPM showing Friction and TDH) alongside the live TDH SVG curve showing both points. The widget does not plot a manufacturer pump curve—compare both TDH points against the pump's published curve so delivered GPM meets or exceeds your design flow.

Mode 2: Backup Battery Runtime Inputs and Outputs

Calculator Input Unit / Format Engineering Role
Battery Voltage (V) V (default 12 V) Multiplies rated Ah to establish nominal watt-hours
Rated Battery Capacity (Ah) Ah (default 100 Ah) Nominal battery rating (enter the manufacturer's usable rating adjusted for expected ambient battery temperature)
Battery Chemistry (DoD) AGM (50%) or LiFePO4 (85%) Sets usable depth of discharge (0.50 or 0.85)
Operating Pump Draw & Unit Watts or DC Amps Battery-side input draw (for AC inverter systems, pre-divide AC pump watts by inverter efficiency P_batt = P_ac / eta_inv)
Controller / Inverter Standby (P_standby) W (default 5 W) Continuous idle draw added to average power (P_avg = P_run * D + P_standby)
Duty Cycle (D) % (0–100%) Fraction of each hour modeled for electrical runtime
Backup Pump Flow at Operating TDH GPM Pump output read from pump curve at your Mode 1 operating TDH
Storm Inflow GPM Sustained storm inflow entering the basin

Mode 2 Outputs: Usable energy (Wh), Battery runtime at selected duty cycle (hr, e.g., 17.14 hr at 25% on 12V 100Ah 50% AGM drawing 120W + 5W standby), Minimum duty cycle to match inflow (%, or 'Exceeds 100% (pump undersized)' when inflow > pump flow), Average battery-side input (at keep-up duty) (W), and Runtime while keeping up with inflow (4.80 hr when 20 GPM inflow = 20 GPM pump forces 100% continuous 125 W draw, or 'Pump cannot keep up with sustained inflow' / 'No hold' in the diagram when inflow > pump flow). Note: Mode 2 uses the entered battery capacity directly and does not apply a temperature curve; for cold basements or garages, enter the battery maker's temperature-derated Ah rating.

How Do You Measure Basin Inflow and Static Lift?

The calculator computes empty vertical-wall basin inflow directly from Basin inside diameter, Measured water rise (in), and Pump-off interval (min). If a large pump housing or thick riser displaces a significant share of the measured band, subtract that submerged displacement (V_disp_gal) manually when verifying field inflow. Static lift (H_static) is strictly the vertical elevation difference between the minimum sump water level and the discharge outlet or vented gravity high point; horizontal runs do not add to H_static.

Vertical-Wall Empty Basin ID Volume per Inch (gal/in) Volume per Foot (gal/ft) Metric Equivalent (L per 25.4 mm)
18 in (457 mm) 1.10 gal/in 13.20 gal/ft 4.16 L
24 in (610 mm) 1.96 gal/in 23.52 gal/ft 7.42 L
Custom ID (D_in) 0.0034 * D_in^2 0.0408 * D_in^2 0.01287 * D_in^2

Plain-Text Inflow Formula (Widget & Manual Displacement Adjustment):

Widget empty-basin inflow:
Q_inflow_gpm = (pi * (D_in / 2)^2 * Delta_h_in / 231) / t_rise_min

Manual adjustment if pump/riser displacement V_disp_gal is significant:
Delta_V_gal = (V_per_in * Delta_h_in) - V_disp_gal
Q_inflow_gpm = Delta_V_gal / t_rise_min

For full field measurement procedures, delayed storm-inflow adjustments, dry-weather underestimation traps, and the 1.25–1.50x peak-storm sizing margin, see How to Measure Sump Pit Inflow Rate and Set a Peak Storm Margin.

How Is Total Dynamic Head (TDH) Calculated Without Double-Counting Fittings?

Total Dynamic Head is the sum of static lift plus flow-dependent pipe friction and minor fitting losses, and both friction and minor losses drop to exactly zero when flow (Q) is zero. The interactive calculator uses Option A — Equivalent Length (Sum(Le)) for single-diameter Sch 40 PVC (C = 150) inside the Hazen-Williams equation; if you perform a manual multi-segment or K-factor calculation outside the widget, choose either Le or K per fitting—never add Le directly to H_static, and never apply both Le and K to the same fitting.

Plain-Text System Curve Equations:

TDH(Q) = H_static + H_friction(Q) + H_minor(Q)

At Q = 0 GPM:
H_friction(0) = 0 ft,  H_minor(0) = 0 ft  =>  TDH(0) = H_static
  • Option A — Equivalent Length Method (used by this calculator for Sch 40 PVC C = 150):
    L_total = L_straight + Sum(Le)
    H_friction(Q) = 10.44 * L_total * (Q_gpm^1.852) / (C^1.852 * d_in^4.8704)
    H_minor(Q) = 0
    
  • Option B — Manual Multi-Segment or Separate Minor-Loss Coefficient Method (Sum(K)):
    v_i (ft/s) = 0.4085 * Q_gpm / (d_in,i^2)
    H_friction,i(Q) = 10.44 * L_straight,i * (Q_gpm^1.852) / (C^1.852 * d_in,i^4.8704)
    H_minor,i(Q) = Sum(K,i) * (v_i^2) / (2 * 32.174)
    

When pipe diameter changes along the discharge path (such as a 1.5 in vertical riser transitioning into a 2.0 in horizontal header), calculate H_friction,i(Q) separately for each segment manually using its own d_in,i and L_i, then sum all segments to build the system curve. For complete PVC roughness (C = 150) friction tables, fitting Le/K lookup values, diameter-effect comparisons, and system-curve intersection walkthroughs, see Sump Pump Total Dynamic Head (TDH) and System Curve Relationships.

When Does Backup Battery Runtime Fail to Equal Flood-Prevention Hours?

Backup battery runtime only estimates how long the battery can power the pump; if the pump's output at operating TDH (Q_pump) is less than sustained storm inflow (Q_inflow), water will continue rising in the basin and can overflow the floor even while the battery still has charge.

Plain-Text Battery Runtime Equations (matching Mode 2):

Usable_Wh = Voltage_V * Capacity_Ah * DoD_fraction

Battery-side run draw:
  Native DC pump:    P_run_W = P_pump_dc_W  (or Voltage_V * Amps_dc)
  AC inverter pump:  P_run_W = P_pump_ac_W / eta_inverter  (enter P_run_W as Operating pump draw)

Selected-duty power & runtime:
  Selected_Duty = Duty_% / 100
  P_selected_W = (P_run_W * Selected_Duty) + P_standby_W
  Battery_Runtime_At_Selected_Duty_hr = Usable_Wh / P_selected_W

Keep-up duty & true storm holdover:
  Required_Duty = min(1.0, Q_inflow / Q_pump)
  Effective_Duty = 1.0 when Q_inflow > Q_pump; otherwise max(Selected_Duty, Required_Duty)
  P_avg_W = (P_run_W * Effective_Duty) + P_standby_W
  Runtime_While_Keeping_Up_hr = null when Q_inflow > Q_pump; otherwise Usable_Wh / P_avg_W
Battery / Architecture Parameter Typical Baseline Range Engineering Impact
Lead-Acid / AGM Depth of Discharge (DoD) 0.50 (50%) Exceeding 50% accelerates sulfation and voltage sag under load
LiFePO4 Depth of Discharge (DoD) 0.80–0.85 (80%–85%) Maintains flatter voltage curve across usable capacity
Native DC Pump Conversion (eta) 1.00 (no inverter) Eliminates DC-to-AC conversion loss and inverter idle draw
AC Inverter Efficiency (eta_inv) 0.80–0.90 (80%–90%) Adds 10%–25% power penalty plus continuous no-load standby draw

Worked Backup Check (12 V, 100 Ah, 50% AGM = 600 Wh, 120 W run, 5 W standby, 25% entered duty):

  • Adequate (20 GPM pump, 5 GPM inflow): Required duty is 25.0% (P_avg = 35 W); Battery runtime at selected duty cycle (25%) and Runtime while keeping up with inflow both read 17.14 hr.
  • Matched / Duty Insufficient (20 GPM pump, 20 GPM inflow, 25% entered duty): Battery runtime at selected duty cycle (25%) still reads 17.14 hr, Minimum duty cycle to match inflow is 100.0 %, average keep-up draw rises to 125 W, and Runtime while keeping up with inflow drops to 4.80 hr (continuous run with zero reserve).
  • Deficit (20 GPM pump, 30 GPM inflow): Water continues rising at 10 GPM; Minimum duty cycle to match inflow prints 'Exceeds 100% (pump undersized)', Runtime while keeping up with inflow prints 'Pump cannot keep up with sustained inflow', and the diagram displays 'No hold'.

What Sizing Prerequisites and Hydraulic Pitfalls Govern Output?

Before sizing or trenching a discharge route, establish a legal stormwater outlet: sump discharge must never enter municipal sanitary sewers, basement floor drains tied to sanitary lines, or residential septic systems, and must not discharge onto neighboring lots or ice public sidewalks. Call 811, wait for utility marks, and separately locate private underground lines before any exterior digging, and never step into standing water contacting energized electrical equipment.

Hydraulic & Capacity Failure Modes

Failure Mode Hydraulic / Physical Cause Observable Symptom Corrective Engineering Action
Undersized Discharge Pipe High velocity (> 8–10 ft/s) spikes H_friction Pump falls far left on curve; low GPM Upsize segment from 1.5 in to 2.0 in ID PVC
Double-Counted Fittings Applying both Le and K to the same elbow or valve Calculated TDH overestimated relative to true system head Apply one fitting method only (Le in widget, or K separately)
Omitted Fittings / Restrictive Elbows Leaving out valves/elbows or choking flow with sharp fittings Calculated TDH underestimated; real pump GPM drops in service Include actual fitting losses; use sweeping elbows and full-flow check valves
Inverter Standby Drain AC inverter left idle for days during intermittent rain Battery depleted before peak storm arrives Account for P_standby_W or use a native DC backup system
Inflow Exceeds Pump Output Q_inflow > Q_pump at true operating TDH Continuous pump run while basin water still rises Reduce TDH, add parallel primary/backup pump capacity, or fix surface grading

For basin short-cycling, float-switch setup, check-valve commissioning, and overall system architecture, see Sump Pumps, Pits & Backup Systems and Sump Pump Sizing, Flow Rate & Total Dynamic Head. For pressure-rated pipe selection, wall penetrations, freeze-relief air gaps, and pressure-to-gravity transitions, see Sump Pump Discharge Piping & Freeze Protection.

DIY Scope vs. Pro / Structural Engineer Thresholds

Condition / Physical Threshold Scope Classification Required Boundary or Action
Shallow discharge work (in verified dry, stable soil) with legal outlet DIY Scope Call 811 + locate private lines; verify legal stormwater outlet; match TDH
Exterior trench depth >= 4–5 ft (1.2–1.5 m) Pro Excavation Threshold Trench collapse hazard; requires proper shoring, sloping, or trench-box protection
Digging near or below foundation footing elevation Pro / Structural Threshold Risks undermining footing bearing support; stop excavation immediately
Multi-wall hydrostatic pressure or chronic high-inflow flooding Pro Drainage / Waterproofing Scope Requires engineered perimeter relief, dual-pump redundancy, and exterior grading
Utility easement, curb core, or public right-of-way crossing Permitted Pro / Municipal Scope Requires municipal permit, inspection, and approved curb/storm-tie detail
Wall bowing, leaning, step-cracking displacement, or active settlement Licensed Structural Engineer (PE) Stop-Line Exits DIY and waterproofing scope; requires on-site licensed PE evaluation

For contractor work packages, pre-backfill inspections, and acceptance testing, see Sump Pump Installation & Upgrade Scope of Work. For ongoing inspection intervals, timed drawdown logs, and planned component replacement thresholds, see Sump Pump Service Logs & Planned Component Replacement.